2 Parameters
2.2 List of parameters
For bit 05:
When know-how protection has been activated, the contents of the memory card (parameter and DCC data) can be
additionally protected against being used with other memory cards. This bit is only set if know-how protection is
active and in p7765 bit 01 is set and not bit 00.
For bit 06:
When know-how protection is activated, the drive data can be traced using the device trace function. This bit is only
set if know-how protection is active and in p7765.2 is set.
p7761
Write protection / Write protection
Access level: 3
Can be changed: U, T
Unit group: -
Min
0
Description:
Setting for activating/de-activating the write protection for adjustable parameters.
Value:
0:
1:
Dependency:
Refer to: r7760
Note:
Parameters with the "WRITE_NO_LOCK" attributes are excluded from the write protection.
A product-specific list of these parameters is also available in the corresponding List Manual.
p7762
Write protection multi-master fieldbus system access behavior / Fieldbus acc_behav
Access level: 3
Can be changed: U, T
Unit group: -
Min
0
Description:
Sets the behavior for write protection when accessing via multi-master fieldbus systems (e.g. CAN, BACnet).
Value:
0:
1:
Dependency:
Refer to: r7760, p7761
p7763
KHP OEM exception list number of indices for p7764 / KHP OEM qty p7764
Access level: 3
Can be changed: U, T
Unit group: -
Min
1
Description:
Sets the number of parameters for the OEM exception list (p7764[0...n]).
p7764[0...n], with n = p7763 - 1
Dependency:
Refer to: p7764
Note:
KHP: Know-How Protection
Even if know-how protection is set, parameters in this list can be read and written to.
p7764[0...n]
KHP OEM exception list / KHP OEM excep list
Access level: 3
Can be changed: U, T
Unit group: -
Min
0
Description:
OEM exception list (p7764[0...n] for setting parameters that should be excluded from know-how protection.
p7764[0...n], with n = p7763 - 1
374
De-activate write protection
Activate write protection
Write access independent of p7761
Write access dependent on p7761
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: -
Unit selection: -
Max
500
Calculated: -
Scaling: -
Unit selection: -
Max
65535
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
1
Data type: Unsigned16
Dyn. index: p7763
Func. diagram: -
Factory setting
[0] 7766
[1...499] 0
List Manual (LH11), 01/2016, A5E33839529