p0775[0...1]
CU analog outputs activate absolute value generation / CU AO absVal act
Access level: 2
Can be changed: T
Unit group: -
Min
0
Description:
Activates the absolute value generation for the analog outputs.
Value:
0:
1:
Index:
[0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Note:
AO: Analog Output
T: Terminal
p0776[0...1]
CU analog outputs type / CU AO type
Access level: 2
Can be changed: U, T
Unit group: -
Min
0
Description:
Sets the analog output type.
p0776[x] = 1 corresponds to a voltage output (p0774, p0778, p0780 are displayed in V).
p0776[x] = 0, 2 corresponds to a current output (p0774, p0778, p0780 are displayed in mA).
Value:
0:
1:
2:
Index:
[0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Note:
When changing p0776, the parameters of the scaling characteristic (p0777, p0778, p0779, p0780) are overwritten
with the following default values:
For p0776 = 0, p0777 is set to 0.0 %, p0778 = 0.0 mA, p0779 = 100.0 % and p0780 to 20.0 mA.
For p0776 = 1, p0777 is set to 0.0 %, p0778 = 0.0 V, p0779 = 100.0 % and p0780 to 10.0 V.
For p0776 = 2, p0777 is set to 0.0 %, p0778 = 4.0 mA, p0779 = 100.0 % and p0780 to 20.0 mA.
p0777[0...1]
CU analog outputs characteristic value x1 / CU AO char x1
Access level: 2
Can be changed: U, T
Unit group: -
Min
-1000.00 [%]
Description:
Sets the scaling characteristic for the analog outputs.
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the x coordinate (percentage) of the 1st value pair of the characteristic.
Index:
[0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Dependency:
Refer to: p0776
Notice:
This parameter is automatically overwritten when changing p0776 (type of analog outputs).
Note:
The parameters for the characteristic do not have a limiting effect.
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
No absolute value generation
Absolute value generation switched in
Current output (0 mA ... +20 mA)
Voltage output (0 V ... +10 V)
Current output (+4 mA ... +20 mA)
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: -
Unit selection: -
Max
2
Calculated: -
Scaling: -
Unit selection: -
Max
1000.00 [%]
2 Parameters
2.2 List of parameters
Data type: Integer16
Dyn. index: -
Func. diagram: 9572
Factory setting
0
Data type: Integer16
Dyn. index: -
Func. diagram: 9572
Factory setting
0
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 9572
Factory setting
0.00 [%]
115