2 Parameters
2.2 List of parameters
Dependency:
The parameter is preset when commissioning the system for the first time and for the factory setting, depending on
the power unit that is connected.
Depending on the setting, the ability to see control parameters is restricted depending on the particular application.
The following applies for p0096 > 0:
The motor data identification routine is preset (p1900 = 12). After the motor data identification, the system
immediately goes into operation.
The following applies for p0096 = 1:
The motor type (p0300) synchronous or reluctance motor is not possible.
Note:
When changing p0096 to 1 or 2, when completing commissioning, fast parameterization should be executed (p3900
> 0).
Depending on the setting, after quick commissioning and/or automatic parameterization, the procedure for motor
data identification as well as the setting of the operating mode and parameterization of the closed-loop control must
be appropriately adapted.
p0100
IEC/NEMA mot stds / IEC/NEMA mot stds
Access level: 1
Can be changed: C(1)
Unit group: -
Min
0
Description:
Defines whether the motor and drive converter power settings (e.g. rated motor power, p0307) are expressed in [kW]
or [hp].
Depending on the selection, the rated motor frequency (p0310) is either set to 50 Hz or 60 Hz.
For p0100 = 0, 2, the following applies: The power factor (p0308) should be parameterized.
For p0100 = 1, the following applies: The efficiency (p0309) should be parameterized.
Value:
0:
1:
2:
Dependency:
If p0100 is changed, all of the rated motor parameters are reset. Only then are possible unit changeovers made.
The units of all motor parameters are changed that are involved in the selection of IEC or NEMA (e.g. r0206, p0307,
r0333, r0334, p0341, p0344, r1969).
Refer to: r0206, p0210, p0300, p0304, p0305, p0307, p0308, p0309, p0310, p0311, p0314, p0320, p0322, p0323,
p0335, r0337, p1800
Note:
The parameter value is not reset when the factory setting is restored (p0010 = 30, p0970).
p0124[0...n]
CU detection via LED / CU detection LED
Access level: 3
Can be changed: U, T
Unit group: -
Min
0
Description:
Identification of the Control Unit using an LED.
Note:
While p0124 = 1, the READY LED flashes green/orange or red/orange with 2 Hz at the appropriate Control Unit.
p0133[0...n]
Motor configuration / Motor config
Access level: 2
Can be changed: C(1, 3)
Unit group: -
Min
-
Description:
Configuration of the motor when commissioning the motor.
Bit field:
Bit
00
01
50
IEC-Motor (50 Hz, SI units)
NEMA motor (60 Hz, US units)
NEMA motor (60 Hz, SI units)
Signal name
Motor connection type
Motor 87 Hz operation
Calculated: -
Scaling: -
Unit selection: -
Max
2
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Delta
Yes
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Unsigned8
Dyn. index: PDS
Func. diagram: -
Factory setting
0
Data type: Unsigned16
Dyn. index: MDS
Func. diagram: -
Factory setting
0000 bin
0 signal
Star
No
List Manual (LH11), 01/2016, A5E33839529