Monitoring torque and load drop
M [Nm]
M_thresh 3 upper
0.00 ... 20000000.00 [Nm]
p2189 [D] (10000000.00)
M_thresh 3 lower
0.00 ... 20000000.00 [Nm]
p2190 [D] (0.00)
M_thresh 2 upper
0.00 ... 20000000.00 [Nm]
p2187 [D] (10000000.00)
M_thresh 2 lower
0.00 ... 20000000.00 [Nm]
p2188 [D] (0.00)
M_thresh 1 upper
0.00 ... 20000000.00 [Nm]
p2185 [D] (10000000.00)
M_thresh 1 lower
0.00 ... 20000000.00 [Nm]
p2186 [D] (0.00)
n_thresh 1
0.00 ... 210000.00 [rpm]
p2182 [D] (150.00)
1
2
Signals and monitoring functions
Load monitoring (part 2)
(p2193 = 1)
Tolerance bandwidth
n_thresh 3
0.00 ... 210000.00 [rpm]
p2184 [D] (1500.00)
n_thresh 2
0.00 ... 210000.00 [rpm]
p2183 [D] (900.00)
3
4
M [Nm]
Stall_mon M_thresh
0.00 ... 20000000.00 [Nm]
p2168 [D] (10000000.00)
M_thresh 3 lower
0.00 ... 20000000.00 [Nm]
p2190 [D] (0.00)
M_thresh 2 lower
0.00 ... 20000000.00 [Nm]
p2188 [D] (0.00)
M_thresh 1 lower
0.00 ... 20000000.00 [Nm]
p2186 [D] (0.00)
M_thresh no load
0.00 ... 20000000.00 [Nm]
p2191 [D] (0.00)
rpm
n_thresh 1
0.00 ... 210000.00 [rpm]
p2182 [D] (150.00)
<1>
Only for pump applications.
5
6
fp_8014_97_54.vsd
09.12.2015
Pump/fan monitoring
(p2193 = 4/5)
Blocked
Pump/fan characteristics
Leakage
<1>
Dry running protection/broken belt
n_thresh 2
0.00 ... 210000.00 [rpm]
p2183 [D] (900.00)
Stall_mon up thr
n_thresh 3
0.00 ... 210000.00 [rpm]
0.00 ... 210000.00 [rpm]
p2165 [D] (0.00)
p2184 [D] (1500.00)
7
Function diagram
G120 CU240B/E-2
V4.7.6
rpm
8
- 8014 -