2 Parameters
2.2 List of parameters
p1974
Speed_ctrl_opt saturation characteristic rotor flux maximum / n_opt rot_fl max
Access level: 4
Can be changed: U, T
Unit group: -
Min
104 [%]
Description:
Sets the maximum flux setpoint to measure the saturation characteristic.
p1980[0...n]
PolID technique / PolID technique
Access level: 3
Can be changed: U, T
Unit group: -
Min
1
Description:
Sets the pole position identification technique.
p1980 = 1, 8: The current magnitude is set using p0329.
p1980 = 4, 6: The current magnitude of the first measurement section is set using p0325, the second using p0329.
p1980 = 10: The rated motor current is impressed to align.
The current magnitudes are limited to the rated power unit values.
Value:
1:
4:
6:
8:
10:
Dependency:
When commissioning a catalog motor, the technique is automatically selected depending on the motor type being
used.
Refer to: p0325, p0329, p1780
Refer to: F07969
Note:
Voltage pulse technique (p1980 = 1, 4) cannot be applied to operation with sine-wave output filters (p0230).
r1984
PolID angular difference / PolID ang diff
Access level: 4
Can be changed: -
Unit group: -
Min
- [°]
Description:
Displays the angular difference between the actual electrical commutation angle and the angle determined by the
pole position identification.
Dependency:
Refer to: p0325, p0329, p1980, r1985, r1987
Note:
When the pole position identification routine is executed several times, the spread of the measured values can be
determined using this value. At the same position, the spread should be less than 2 degrees electrical.
r1985
PolID saturation curve / PolID sat_char
Access level: 4
Can be changed: -
Unit group: -
Min
- [Arms]
Description:
Displays the saturation characteristic of the pole position identification routine (saturation technique).
Displays the current characteristic of the pole position identification routine (elasticity technique).
Dependency:
Refer to: p0325, p0329, p1980, r1984, r1987
270
Voltage pulsing 1st harmonic
Voltage pulsing 2-stage
Voltage pulsing 2-stage inverse
Voltage pulsing 2nd harmonic, inverse
DC current injection
Calculated: p0340 = 1
Scaling: -
Unit selection: -
Max
120 [%]
Calculated: p0340 = 1,3
Scaling: -
Unit selection: -
Max
10
Calculated: -
Scaling: -
Unit selection: -
Max
- [°]
Calculated: -
Scaling: -
Unit selection: -
Max
- [Arms]
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
120 [%]
Data type: Integer16
Dyn. index: MDS
Func. diagram: -
Factory setting
4
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [°]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [Arms]
List Manual (LH11), 01/2016, A5E33839529