Siemens SINAMICS G120 List Manual page 343

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

p3110
External fault 3 switch-on delay / Ext fault 3 t_on
Access level: 3
Can be changed: U, T
Unit group: -
Min
0 [ms]
Description:
Sets the delay time for external fault 3.
Dependency:
Refer to: p2108, p3111, p3112
Refer to: F07862
p3111[0...n]
BI: External fault 3 enable / Ext fault 3 enab
Access level: 3
Can be changed: U, T
Unit group: -
Min
-
Description:
Sets the signal source for the enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency:
Refer to: p2108, p3110, p3112
Refer to: F07862
p3112[0...n]
BI: External fault 3 enable negated / Ext flt 3 enab neg
Access level: 3
Can be changed: U, T
Unit group: -
Min
-
Description:
Sets the signal source for the negated enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency:
Refer to: p2108, p3110, p3111
Refer to: F07862
r3113.0...15
CO/BO: NAMUR message bit bar / NAMUR bit bar
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Display and BICO output for the status of the NAMUR message bit bar.
The faults and alarms are assigned to the appropriate signaling/message classes and influence a specific message
bit.
Bit field:
Bit
00
01
02
03
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Signal name
Fault converter information
electronics/software error
Network fault
DC-link overvoltage
Fault drive converter power electronics
Calculated: -
Scaling: -
Unit selection: -
Max
1000 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
2 Parameters
2.2 List of parameters
Data type: Unsigned16
Dyn. index: -
Func. diagram: 2546
Factory setting
0 [ms]
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: -
Factory setting
1
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: -
Factory setting
0
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
-
0 signal
No
No
No
No
FP
-
-
-
-