2 Parameters
2.2 List of parameters
r2109[0...63]
Fault time removed in milliseconds / t_flt resolved ms
Access level: 3
Can be changed: -
Unit group: -
Min
- [ms]
Description:
Displays the system runtime in milliseconds when the fault was removed.
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2130, r2133, r2136
Notice:
The time comprises r2136 (days) and r2109 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
r2110[0...63]
Alarm number / Alarm number
Access level: 2
Can be changed: -
Unit group: -
Min
-
Description:
This parameter is identical to r2122.
p2111
Alarm counter / Alarm counter
Access level: 3
Can be changed: U, T
Unit group: -
Min
0
Description:
Number of alarms that have occurred after the last reset.
Dependency:
When p2111 is set to 0, the following is initiated:
- all of the alarms of the alarm buffer that have gone [0...7] are transferred into the alarm history [8...63].
- the alarm buffer [0...7] is deleted.
Refer to: r2110, r2122, r2123, r2124, r2125
Note:
The parameter is reset to 0 at POWER ON.
p2112[0...n]
BI: External alarm 1 / External alarm 1
Access level: 3
Can be changed: U, T
Unit group: -
Min
-
Description:
Sets the signal source for external alarm 1.
Dependency:
Refer to: A07850
Note:
An external alarm is triggered with a 1/0 signal.
r2114[0...1]
System runtime total / Sys runtime tot
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Displays the total system runtime for the drive unit.
The time comprises r2114[0] (milliseconds) and r2114[1] (days).
After r2114[0] has reached a value of 86.400.000 ms (24 hours) this value is reset and r2114[1] is incremented.
300
Calculated: -
Scaling: -
Unit selection: -
Max
- [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
65535
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: Unsigned32
Dyn. index: -
Func. diagram: 8050, 8060
Factory setting
- [ms]
Data type: Unsigned16
Dyn. index: -
Func. diagram: 8065
Factory setting
-
Data type: Unsigned16
Dyn. index: -
Func. diagram: 8050, 8065
Factory setting
0
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2546
Factory setting
1
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
-
List Manual (LH11), 01/2016, A5E33839529

Advertisement

Table of Contents
loading

Table of Contents