Siemens G130 List Manual page 1905

Hide thumbs Also See for G130:
Table of Contents

Advertisement

A35907 (F, N)
TM: Hardware initialization error
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
B_INF, TM120, TM150, TM31, VECTOR_G
Component:
Terminal Module (TM)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The Terminal Module was not successfully initialized.
Alarm value (r2124, interpret hexadecimal):
01: TM17 or TM41 - incorrect configuration request.
02: TM17 or TM41 - programming not successful.
04: TM17 or TM41 - invalid time stamp
Remedy:
Carry out a POWER ON.
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A35910 (F, N)
TM: Module overtemperature
Message value:
-
Message class:
Overtemperature of the electronic components (6)
Drive object:
B_INF, TM120, TM150, TM31, VECTOR_G
Component:
Terminal Module (TM)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature in the module has exceeded the highest permissible limit.
Remedy:
- reduce the ambient temperature.
- replace the Terminal Module.
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A35911 (F, N)
TM: Clock synchronous operation sign-of-life missing
Message value:
-
Message class:
Communication error to the higher-level control system (9)
Drive object:
B_INF, TM120, TM150, TM31, VECTOR_G
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
The maximum permissible number of errors in the master sign-of-life (clock synchronous operation) has been
exceeded in cyclic operation.
When the alarm is output, the module outputs are reset up to the next synchronization.
Remedy:
- check the physical bus configuration (terminating resistor, shielding, etc.).
- check the interconnection of the master sign-of-life (r4201 via p0915).
- check whether the master correctly sends the sign-of-life (e.g. set up a trace with r4201.12 ... r4201.15 and trigger
signal r4301.9).
- check the bus and master for utilization level (e.g. bus cycle time Tdp was set too short).
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
BICO
Propagation:
BICO
Propagation:
BICO
4 Faults and alarms
4.2 List of faults and alarms
1905

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents