4 Faults and alarms
4.2 List of faults and alarms
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A35411 (F, N)
TM: Temperature alarm threshold channel 5 exceeded
Message value:
%1
Message class:
External measured value / signal state outside the permissible range (16)
Drive object:
B_INF, TM150, VECTOR_G
Component:
Terminal Module (TM)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature (r4105[5]) measured using the temperature sensing of the Terminal Module 150 (TM150) has
exceeded the threshold value to initiate this alarm (p4102[10]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[5] = 1, 4), the following applies:
- if r4101[5] > 1650 ohms, the temperature r4105[5] = 250 °C
- if r4101[5] <= 1650 ohms, the temperature r4105[5] = -50 °C
Alarm value (r2124, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
Allow the temperature sensor to cool down to below p4102[10] - hysteresis (p4118[5]).
See also: p4102
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A35412 (F, N)
TM: Temperature alarm threshold channel 6 exceeded
Message value:
%1
Message class:
External measured value / signal state outside the permissible range (16)
Drive object:
B_INF, TM150, VECTOR_G
Component:
Terminal Module (TM)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature (r4105[6]) measured using the temperature sensing of the Terminal Module 150 (TM150) has
exceeded the threshold value to initiate this alarm (p4102[12]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[6] = 1, 4), the following applies:
- if r4101[6] > 1650 ohms, the temperature r4105[6] = 250 °C
- if r4101[6] <= 1650 ohms, the temperature r4105[6] = -50 °C
Alarm value (r2124, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
Allow the temperature sensor to cool down to below p4102[12] - hysteresis (p4118[6]).
See also: p4102
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
1892
Propagation:
BICO
Propagation:
BICO
List Manual (LH2), 07/2016, A5E03263479A
SINAMICS G130/G150