Connecting To Sdc15, Sdc25/26 Or Sdc35/36 - Mitsubishi Electric GT16 User Manual

Got1000 series
Hide thumbs Also See for GT16:
Table of Contents

Advertisement

52.5.3 Connecting to SDC15,
SDC25/26 or SDC35/36
Communication settings
Make the communication settings by operating the key
or Smart Loader Package (SLP-C35) of the
temperature controller.
Item
*1
9600bps, 19200bps
Transmission speed
*2
CPL
Communication mode
*1
7bits, 8bits
Data bit
*1
Odd, even, none
Parity bit
*1
1bit, 2bits
Stop bit
Communication minimum
1 to 250ms
response time
*3*4
0 to 127
Station address
*1
The transmission speed setting must be consistent with that
of the GOT side.
*2
Set to CPL.
*3
Do not set to "0".
*4
Select the station address without overlapping with that of
other units.
52.5.4 Connecting to SDC20/21,
SDC30/31
Communication settings
Make the communication settings by operating the key
of the temperature controller.
Item
*1
9600bps
Transmission speed
Data bit
8bits
Parity bit
Disable
Stop bit
2bits
*2*3
0 to 127
Station address
*1
The transmission speed setting must be consistent with that
of the GOT side.
*2
Do not set to "0".
*3
Select the station address without overlapping with that of
other units.
52.5.5 Connecting to CMC10L
Communication settings
Make the communication settings by operating the DIP
switch of the control equipment.
Item
*1
Transmission speed
*2
Frame length
*1
The transmission speed setting must be consistent with that
of the GOT side.
*2
The sum of data length, parity bit and stop bit
52 - 20
52. CONNECTION TO AZBIL CONTROL EQUIPMENT
52.5 Control Equipment Side Setting
Set value
Set value
Set value
9600bps, 19200bps, 38400bps
9 to 15bits
Settings by switch
Front view of CMC10L body
(1) Setting DIP switches
(a) Transmission speed settings
Switch No.
Transmission
speed (bps)
1
2
9600
ON
OFF
19200
OFF
ON
38400
ON
ON
(b) Frame length settings
Switch No.
Frame length
4
5
8bits
OFF
OFF
9 bits
ON
OFF
10 bits
OFF
ON
11 bits
ON
ON
12 bits
OFF
OFF
13 bits
ON
OFF
14 bits
OFF
ON
15 bits
ON
ON
(c) Connecting terminating resistors
Switch No.
Terminating
resistor
8
Enable
ON
Disable
OFF
(2) Mode selector switch settings
Set the switch to "TERMINAL".
DIP switch
Mode selector
switch
Rear view of CMC10L body
3
Set these
switches
ON
ON
ON
6
OFF
OFF
Set these
OFF
switches
OFF
ON
ON
ON
ON
Set these
switches