Mitsubishi Electric GT16 User Manual page 1042

Got1000 series
Hide thumbs Also See for GT16:
Table of Contents

Advertisement

RS485 connection diagram 5)
Interface
*4
converter side
(CMC10L)
DA
11
DB
12
SG
13
*1
Pin No. of control equipment differs depending on the model. Refer to the following table.
Signal name
DA
DB
SG
*2
Terminating resistor should be provided for an interface converter and a control equipment which will be terminals.
*3
Connect FG grounding to the single-sided end of a cable shield line.
*4
Since the interface converter has a built-in terminating resistor, set the terminating resistor of GOT to "Enable".
For details of terminating resistor settings, refer to the following.
Precautions when preparing a cable
(1) Cable length
(a) The length of the RS-485 cable used for
connecting the control equipment to the
communication converter
The length of the RS-485 cable must be 500m or
less.
(b) The length of the RS-485 cable used for
connecting the control equipment to the GOT
The total distance (between GOT and controllers)
of RS-485 cable must be 13m or less.
(2) Connector conversion box side connector
For the Connector conversion box side connector, refer
to the following.
6.7 Connector Conversion Box
(3) AZBIL control equipment side connector
Use the connector compatible with the AZBIL control
equipment side module.
For details, refer to the user's manual of the AZBIL
control equipment.
52 - 16
52. CONNECTION TO AZBIL CONTROL EQUIPMENT
52.3 Connection diagram
Terminating resistor(150Ω 1/2W)
Control equipment
side
* 1
DA
DB
SG
* 3
Model of control equipment
CMS
SDC45/46
CMF015
Pin No.
Pin No.
Pin No.
C10
5
C11
6
C12
10
52.5.5 Connecting to CMC10L
*2
Control
equipment
side
* 3
MQV
MVF
RX
MPC
Pin No.
Pin No.
7
1
1
8
2
2
9
7
3
Connecting terminating resistors
(1) GOT side
When connecting a PLC to the GOT, a terminating
resistor must be connected to the GOT.
For the procedure to set the terminating resistor, refer
to the following.
4.2 Back Panel
(2) AZBIL control equipment side
When connecting a AZBIL control equipment to the
GOT, a terminating resistor must be connected.
52.5 Control Equipment Side Setting
* 1
DA
DB
SG