Testing Wriststrap Grounding Cords Rlcm - Nortel DMS-100 Series Maintenance Manual

Remote line concentrating module
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

13-12
13-12
Routine maintenance procedures
Testing wriststrap grounding cords
RLCM
Application
Use this procedure to verify the resistance of the wriststrap grounding cords
is at the correct level. The resistance must be low enough to allow static
electricity to discharge from a person. The resistance must also be high
enough to protect the wearer from electrocution if the equipment
short-circuits.
Interval
Perform this procedure each month.
Common procedures
There are no common procedures.
Action
This procedure contains a summary flowchart and a list of steps. Use the
flowchart to review the procedure. Follow the steps to perform the
procedure.
297–8351–550 Standard 04.01 August 1999
13-12