Rlcm Critical - Nortel DMS-100 Series Maintenance Manual

Remote line concentrating module
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

7-2
7-2
RLCM alarm clearing procedures
RLCM
critical
Alarm display
CM
.
Indication
At the MAP subsystem display, the LCM alarm appears under the PM
header. This alarm indicates an alarm condition in the RLCM. The n
indicates the number of RLCMs with alarms. The *C* that appears under
the alarm indicates the alarm class is critical.
Use this procedure to recover service in an RLCM when both units of the
line concentrating module (LCM) are out of service. This condition always
produces a central side busy (CBsy) alarm.
Meaning
The LCM is system busy (SysB) or C-side busy (CBsy). An LCM is SysB if
both units are SysB or if one unit is SysB and the other unit is manual busy
(ManB). An LCM is CBsy when both units of the LCM are CBsy.
Result
When an LCM is SysB or CBsy, call processing ceases. This condition
results in a critical alarm indication.
Common procedures
There are no common procedures.
Action
This procedure contains a summary flowchart and a list of steps. Use the
flowchart to review the procedure. Follow the steps to perform the
procedure.
Note: The numbers represented in the flowchart do not coincide with the
step-action numbers. The numbers indicate movement in the flowchart.
297–8351–550 Standard 04.01 August 1999
7-2
MS
IOD
Net
.
.
.
PM
CCS
Lns
nLCM
.
.
*C*
Trks
Ext
Appl
.
.
.