Nortel DMS-100 Series Maintenance Manual page 401

Remote line concentrating module
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

Replacing an NT3X09 card in an RMM
At your current location
1
Obtain a replacement card. Ensure that the replacement card has the same
product equipment code (PEC), including suffix, as the card to be removed.
At the MAP terminal
2
Access the TTP level of the MAP terminal and post the RMM that contains the
card to be replaced by typing
>MAPCI;MTC;TRKS;TTP;POST P RMM rmm_no ckt_no
and pressing the Enter key.
where
rmm_no
is the number of the RMM shelf in which the card is to be replaced
ckt_no
is the number of the first circuit where the NT3X09 card is physically
located
Example of a MAP response:
LAST CIRCUIT = 27
POST CKT IDLED
SHORT CLLI IS:
OK, CLLI POSTED
POST
20
DELQ
TTP 6–006
CKT TYPE
PM NO.
OG
MISC RMM 0 0
3
Check the status of the RMM.
If RMM status is
MB, PMB, RMB
other
4
Busy the trunks that are associated with the card to be replaced by typing
>BSY ; NEXT
and pressing the Enter key.
Note: Repeat this step for all circuits associated with the faulty NT3X09 card to
be replaced.
DMS-100 Family RLCM Maintenance Manual XPM12 and up
Card replacement procedures 8-83
1118
BUSY Q
COM LANG
MTADRIVER 20
RMM
(continued)
DIG
STA S R DOT TE R
LO
Do
step 5
step 4
NT3X09