Nortel DMS-100 Series Maintenance Manual page 305

Remote line concentrating module
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

Summary of RMM minor alarm
At PM level of
MAP display
ISTb RMMs
Post RMM
3
Test RMM
1
Test passes?
N
C-side links
not
available?
N
Card list
received?
N
4
Test passes?
2
N
4
Y
End of
procedure
Y
Post C-side
RLCM
Y
Replace card
Y
Return link to
service
DMS-100 Family RLCM Maintenance Manual XPM12 and up
RLCM alarm clearing procedures 7-121
This flowchart summarizes the
procedure.
Use the instructions that follow
this flowchart to perform the
procedure.
Display P-side
Busy and test
link that has
link that has
defects
defects
Contact
maintenance
1
4
support group
Y
RTS passes?
N
4
RMM
minor
(continued)
5
2
Y
Do other links
5
have defects?
N
3