7-132 RLCM alarm clearing procedures
ESA
critical, minor
(continued)
12
13
14
15
297–8351–550 Standard 04.01 August 1999
To identify the ISTb ESA processor, type
>DISP ISTB ESA
and press the Enter key.
To post the ESA processor with the alarm condition, type
>POST ESA esa_no
and press the Enter key.
where
esa_no
is the number of the ESA processor (0 to 255)
Example of a MAP response:
REM1
ESA
0 SysB
To busy the posted ESA processor, type
>BSY
and press the Enter key.
Example of MAP response:
This action will take this PM out of service
Please confirm ("Yes" or "No")
To confirm busy, type
>YES
and press the Enter key.
To test the ESA processor, type
>TST
and press the Enter key.
If test
passes
fails because of loading errors
fails, and system produces card
list
fails, and system does not
produce card list
Do
step 18
step 16
step 17
step 20