Nortel DMS-100 Series Maintenance Manual page 389

Remote line concentrating module
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

47
Return LCM unit 1 to service by typing
>RTS UNIT 1
and pressing the Enter key.
If RTS
passed
failed
48
Post the ESA processor associated with the faulty NT2X70 card by typing
>POST ESA esa_no
and pressing the Enter key.
where
esa_no
is the number of the ESA processor identified in step 4.
49
Load the ESA processor by typing
>LOADPM
and pressing the Enter key.
If
message "loadfile not found in
directory" is not received
load passed
load failed
50
Determine the type of device on which the PM load files are located.
If load files are located on
tape
IOC disk
SLM disk
51
Locate the tape that contains the PM load files.
DMS-100 Family RLCM Maintenance Manual XPM12 and up
Card replacement procedures 8-71
HIE
Do
step 48
step 73
Do
step 50
step 68
step 73
Do
step 51
step 57
step 62
NT2X70
(continued)