Nortel DMS-100 Series Maintenance Manual page 387

Remote line concentrating module
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

39
Busy the ESA processor by typing
>BSY
and pressing the Enter key.
Example of a MAP response:
This action will take this PM out of service
Please confirm ("Yes" or "No")
Respond to the system prompt by typing
>YES
At the HIE shelf
40
WARNING
Static electricity damage
Wear a wrist strap connected to the wrist strap
grounding point of a frame supervisory panel (FSP)
while handling circuit cards. This protects the cards
against damage caused by static electricity.
Power down the NT2X70 card in slot 22 of the HIE shelf by setting the ON/OFF
switch on the power converter faceplate to the OFF position. Both the
converter FAIL LED and FRAME FAIL lamp on the frame supervisory panel
(FSP) will be ON. An audible alarm may sound. If an alarm does sound,
silence it by typing
>SIL
and pressing the Enter key.
If NT2X70 is in
shelf 38 slot 25
shelf 38 slot 22
Note: For the NTNX14AA cabinet the circuit breaker assignments are:
NTNX14AA cabinet
shelf 33 slot 25
shelf 33 slot 22
DMS-100 Family RLCM Maintenance Manual XPM12 and up
Card replacement procedures 8-69
HIE
trip circuit breaker
CB1 on FSP
CB4 on FSP
trip circuit breaker
CB3 on FSP
CB8 on FSP
NT2X70
(continued)