Nortel DMS-100 Series Maintenance Manual page 372

Remote line concentrating module
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

8-54 Card replacement procedures
NT2X59
RMM
(continued)
Summary of card replacement procedure for an NT2X59 card in an RMM
At MAP PM level,
post the RMM
BSY the RMM
Replace the card
with one with
identical PEC
Directed to
this proc from
other proc?
Return the RMM to
service
297–8351–550 Standard 04.01 August 1999
Return to alarm
Y
clearing or other
procedure
N
End of procedure
This flowchart summarizes the
procedure.
Use the instructions in the
procedure that follows this
flowchart to perform the
procedure.