Nortel DMS-100 Series Maintenance Manual page 190

Remote line concentrating module
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

7-6 RLCM alarm clearing procedures
RLCM
critical
(continued)
Recovering an out-of-service RLCM
At the MAP terminal
1
2
3
4
5
6
297–8351–550 Standard 04.01 August 1999
Make sure that the RLCM is receiving power.
To silence an audible alarm, type
>MAPCI;MTC;SIL;PM
and press the Enter key.
To identify the RLCM that has faults, type
>DISP STATE CBSY LCM
and press the Enter key.
If response
indicates CBsy LCMs are not
present
indicates CBsy LCMs are present
To post the RLCM with the alarm condition, type
>POST LCM CBSY
and press the Enter key.
Note: Note the name and number of this RLCM.
To identify central side (C-side) links to the host PM, type
>TRNSL C
and press the Enter key.
Example of a MAP response:
Link 0: LTC 0
Link 1: LTC 0
To post the host PM, type
>POST pm pm_no
and press the Enter key.
where
pm
is a line group controller (LGC), line trunk controller (LTC), or remote
cluster controller (RCC)
pm_no
is the number of the PM
Do
step 14
step 4
2; Cap MS; Status: SysB
6; Cap MS; Status: SysB
;MsgCond: CLS
;MsgCond: CLS