Nortel DMS-100 Series Maintenance Manual page 548

Remote line concentrating module
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

8-230 Card replacement procedures
NTEX54
RLCM
(continued)
8
9
10
297–8351–550 Standard 04.01 August 1999
To manually busy the logical drawer, type
>BSY DRWR drwr_no
and press the Enter key.
where
drwr_no
is the logical drawer number (0 to 23)
Example of a MAP response:
LCM REM1 01 1
Drwr 0 will be taken out of service
Please confirm ("YES", "Y", "NO", or "N"):
To confirm the command, type
>YES
and press the Enter key.
Example of a MAP response:
LCM REM1 01 1
Drwr 0 Bsy Passed
If
you must busy the other logical
drawer of the pair
both logical drawers are now M
Busy the other logical drawer of the pair.
>BSY DRWR drwr_no
and press the Enter key.
where
drwr_no
is the logical drawer number (0 to 23)
Example of a MAP response:
LCM REM1 01 1
Drwr 0 Bsy Passed
Do
step 10
step 11