7-36 RLCM alarm clearing procedures
RLCM talk battery alarm
critical
(continued)
28
29
30
At the RLCM site
31
297–8351–550 Standard 04.01 August 1999
To access the CARRIER level of the MAP display, type
>TRKS;CARRIER
and press the Enter key.
To post the host XPM P-side links, type
>POST pm_type pm_no link_no
and press the Enter key.
where
pm_type
is the host peripheral (LGC, LTC, RCC, or RCC2)
pm_no
is the number of the peripheral (0 to 255)
link_no
is the number of the link with the host XPM. Refer to
step 24 display.
To view additional links, use the NEXT command when the system prompts
with the MORE ... prompt.
Example of a MAP response:
N CLASS SITE LTC CK D ALRM SLIP FRME BER
0 REMOTE HOST 0
To offline the links to prevent alarms and to reset the counters when the links
restore, type
>OFFL item_no
and press the Enter key.
where
is the item number under the n (0 to 4) column
item_no
Note: Perform this step for each link busied in step 27.
Remove the fuses and unseat the repeaters for the affected LCM unit.
If the affected LCM unit
is unit 0
is unit 1
0 C
0
0
Host XPM P-side link number
Do
step 32
step 33
ES SES STATE
1
0
0
ManB