Nortel DMS-100 Series Maintenance Manual page 397

Remote line concentrating module
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

6
Use the following information to determine the next step in this procedure.
If you entered this procedure
from an alarm clearing procedure
from other
At the MAP display
7
Test the RMM by typing
>TST
and pressing the Enter key.
Example of a MAP response:
Test Passed
or
Test Failed
If the TST
passes
fails
8
Return the RMM to service by typing
>RTS
and pressing the Enter key.
If the RTS
passes
fails
9
Send any faulty cards for repair according to local procedure.
10
Record the following items in office records:
date the card was replaced
serial number of the card
symptoms that prompted replacement of the card.
DMS-100 Family RLCM Maintenance Manual XPM12 and up
Card replacement procedure 8-79
RMM
(continued)
Do
step 12
step 7
Do
step 8
step 13
Do
step 9
step 13
NT2X90