8-48 Card replacement procedures
NT2X48
NT2X48
RMM
RMM
(continued)
(end)
8
9
10
11
12
297–8351–550 Standard 04.01 August 1999
Installation busy the trunks that are associated with the new NT2X48 card by
typing
>BSY INB ALL
and pressing the Enter key.
Note: ESA digitone receivers should always be in an INB state when the
RLCM is under CC control, to prevent CC access. The ESA
processor will turn the circuits up to an idle state when the RLCM is in
the ESA environment.
Send any faulty cards for repair according to local procedure.
Record the following items in office records:
date the card was replaced
serial number of the card
symptoms that prompted replacement of the card
Go to step 12.
Obtain further assistance in replacing this card by contacting the personnel
responsible for higher level of support.
You have completed this procedure.