6.2 Operation for Momentary Power Interruptions

6.2

Operation for Momentary Power Interruptions

Even if the main power supply to the SERVOPACK is interrupted momentarily, power supply to
the motor (servo ON status) will be maintained for the time set in Pn509 (Momentary Power
Interruption Hold Time).
Pn509
(2509
hex)
If the momentary power interruption time is equal to or less than the setting of Pn509, power
supply to the motor will be continued. If it is longer than the setting, power supply to the motor
will be stopped. Power will be supplied to the motor again when the main circuit power supply
recovers.
Main circuit
power supply
Setting of
Pn509
Motor power
status
Information
Important
6-14
Momentary Power Interruption Hold Time
Setting Range
Setting Unit
20 to 50,000
Setting of Pn509 ≥ Momentary power interruption time
Momentary power interruption
Momentary power
interruption ≤ Pn509
Pn509
Power supply
continued.
Power supplied.
Momentary power interruption
1. If the momentary power interruption time exceeds the setting of Pn509, the /S-RDY (Servo
Ready) signal will turn OFF.
2. If uninterruptible power supplies are used for the control power supply and main circuit
power supply, the SERVOPACK can withstand a power interruption that lasts longer than
50,000 ms.
3. The holding time of the SERVOPACK control power supply (24 VDC) depends on the
specifications of the 24-VDC power supply. Confirm the holding time yourself. If control
operations become impossible during a momentary power interruption of the control
power supply, the setting of Pn509 will be ignored and the same operation will be per-
formed as for when the power supply is turned OFF normally.
The holding time of the main circuit power supply depends on the output from the SERVOPACK.
If the load on the Servomotor is large and an A.410 alarm (Undervoltage) occurs, the setting of
Pn509 will be ignored.
Default Setting
1 ms
20
Setting of Pn509 < Momentary power interruption time
Main circuit
power supply
Setting of
Pn509
Motor power
status
Speed
Position
When Enabled
Immediately
Momentary power interruption
Pn509
Power not
supplied.
Power supplied.
Power shut OFF.
Momentary power interruption
Torque
Classification
Setup
Momentary power
interruption > Pn509