Alarm Code:
Possible Cause
Alarm Name
Fluctuation in the Eth-
erCAT communica-
tions synchronization
EA2 hex:
timing (Sync0) caused
Command-
the synchronization
Option IF Servo
timing in the SERVO-
Synchronization
PACK to fluctuate.
Error
A failure occurred in
the SERVOPACK.
Noise caused an error
EA3 hex:
in communications in
Command-
the SERVOPACK.
Option IF Servo
A failure occurred in
Data Error
the SERVOPACK.
The delay between
activation of the
/HWBB1 and
Eb1 hex:
/HWBB2 input sig-
Safety Function
nals for the HWBB
Signal Input Tim-
was ten second or
ing Error
longer.
A failure occurred in
the SERVOPACK.
EC8 hex:
Gate Drive Error 1
(An error
occurred in the
gate drive circuit.)
EC9 hex:
A failure occurred in
Gate Drive Error
the SERVOPACK.
2
(An error
occurred in the
gate drive cir-
cuit.)
Ed1 hex:
A timeout error
occurred for an Ether-
Command Exe-
CAT command.
cution Timeout
The three-phase
power supply wiring is
F10 hex:
not correct.
Power Supply
The three-phase
Line Open Phase
power supply is
(The voltage was
unbalanced.
low for more than
one second for
phase R, S, or T
when the main
A failure occurred in
power supply
the SERVOPACK.
was ON.)
Confirmation
Turn the power supply
OFF and ON again and re-
establish communica-
tions.
Repair or replace the
SERVOPACK.
Implement countermea-
sures against noise.
Replace the SERVO-
PACK.
The output signal circuits
or devices for /HWBB1
and /HWBB2 or the SER-
VOPACK input signal cir-
Measure the time delay
cuits may be faulty.
between the /HWBB1
Alternatively, the input sig-
and /HWBB2 signals.
nal cables may be discon-
nected. Check to see if
any of these items are
faulty or have been dis-
connected.
Replace the SERVO-
PACK.
Turn the power supply to
the SERVOPACK OFF and
ON again. If an alarm still
occurs, the SERVOPACK
may be faulty. Replace the
SERVOPACK.
Execute the Servo ON
Check the motor status
command (Enable Opera-
when the command is
tion command) only when
executed.
the motor is not operat-
ing.
Check the power sup-
Make sure that the power
ply wiring.
supply is correctly wired.
Measure the voltage for
each phase of the
Balance the power sup-
three-phase power sup-
ply by changing phases.
ply.
Turn the power supply to
the SERVOPACK OFF and
ON again. If an alarm still
occurs, the SERVOPACK
may be faulty. Replace the
SERVOPACK.
15.2 Alarm Displays
15.2.2 Troubleshooting Alarms
Continued from previous page.
Correction
Reference
page 4-11