6.13 Forcing the Motor to Stop
6.13.2 Stopping Method Selection for Forced Stops
Stopping the Servomotor by Setting Emergency Stop
Torque (Pn406)
To stop the Servomotor by setting emergency stop torque, set Pn406 (Emergency Stop
Torque).
If Pn001 = n.X is set to 1 or 2, the Servomotor will be decelerated to a stop using the
torque set in Pn406 as the maximum torque.
The default setting is 800%. This setting is large enough to allow you to operate the Servomo-
tor at the maximum torque. However, the maximum emergency stop torque that you can actu-
ally use is the maximum torque of the Servomotor.
Pn406
(2406
hex)
*
Set a percentage of the motor rated torque.
Stopping the Servomotor by Setting the Deceleration Time
for Servo OFF and Forced Stops (Pn30A)
To specify the Servomotor deceleration time and use it to stop the Servomotor, set Pn30A
(Deceleration Time for Servo OFF and Forced Stops).
Pn30A
(230A
hex)
If you set Pn30A to 0, the Servomotor will be stopped with a zero speed.
The deceleration time that you set in Pn30A is the time to decelerate the motor from the maxi-
mum motor speed.
Maximum speed
Operating speed
6-56
Emergency Stop Torque
Setting Range
Setting Unit
0 to 800
Deceleration Time for Servo OFF and Forced Stops
Setting Range
Setting Unit
0 to 10,000
Default Setting
1%*
800
Default Setting
1 ms
0
Actual deceleration time
Actual
deceleration time
Pn30A
Speed
Position
When Enabled
Classification
Immediately
Speed
Position
When Enabled
Classification
Immediately
Operating speed
× Deceleration time (Pn30A)
=
Maximum speed
Setup
Setup