17.4.1 FAN Replacement
This section describes the procedure to replace FANs inside an MG-SIP128 [MG-
128SIPMGG].
* A failure of a cooling FAN rises the temperature inside of an MG-SIP128 [MG-
128SIPMGG], which greatly influences the system. Please replace a cooling FAN every
five years to avoid it, even though the cooling FAN still works normally.
[Replacement Procedure]
Note:
You can replace cooling FANs as the MG-SIP128 [MG-128SIPMGG] remains on.
Step1:
Use a Phillips driver to loosen a screw at the left side of the FAN cover on the rear panel
of an MG-SIP128 [MG-128SIPMGG].
Step2:
Slide the FAN cover to the left to remove.
VOL.2-1355
MG-SIP128 [MG-128SIPMGG]
ATTENTION
Contents
Static Sensitive
Handling
Precautions Required