A S S e r i e s P r o g r a m m i n g M a n u a l
CANopen communication is in the BUS-
19F4
OFF state.
The sending registers exceed the
19FB
range.
The receiving registers exceed the
19FC
range.
Not using the FCOMP card or not in the
right mode for the ASDA-A2 while using
2001
the CANopen communication
instruction.
The device used in the program
2003
exceeds the device range or it is illegal.
The operand n or the other constant
200B
operands K/H exceed the range.
200C
The operands overlap.
The binary to binary-coded decimal
200D
conversion is incorrect.
200E
The string does not end with 00.
2012
Incorrect division operation
The value exceeds the range of values
2013
that can be represented by the floating-
point numbers.
The task designated by the TKON or
2014
YKOFF instruction is incorrect or
exceeds the range.
_7
The instruction BREAK is written
2017
outside of the FOR-NEXT loop.
No such position planning table number
2027
or the format is incorrect.
High speed output instruction is being
2028
executed. Only one instruction can be
executed at a time.
The output frequency executed by
2030
CSFO instruction exceeds the
maximum output frequency.
If the input pulse is 0 Hz and lasts for
2031
more than 2 seconds, PLC stops
outputting automatically.
6004
The IP address filter is set incorrectly.
600D
RJ45 port is not connected.
7 - 1 2
authorized distributors.
1. Check if the network cable is normal and the
shielded cable is grounded.
2. Check if the start and end of the network cable
are both connected with a 121Ω terminal
resistor.
3. Check if all the node devices run at the same
baud rate on the network.
Revise the time to synchronize (suggested to use a
longer time).
Revise the time to synchronize (suggested to use a
longer time).
1. Use the FCOMP card in the function card 2 slot
and make sure its work mode is CANopen
communicaiton.
2. Check the position where an error occurs and
modify the program. Compile the program and
download the program again.
Check the position where an error occurs and
modify the program. Compile the program and
download the program again.
1. Check the position where an error occurs and
modify the program. Compile the program and
download the program again.
2. Check the settings in the position planning table.
Refer to SR28 for the record of the axis number and
rearrange the output control procedures.
Modify the ratio of input and output frequency or
lower the input frequency.
Modify the ratio of input and output frequency or
lower the input frequency.
Set the Ethernet parameter for the CPU module in
HWCONFIG again.
Check the connection.
-