List Of Commands - Mitsubishi Electric GT16 User Manual

Got1000 series
Hide thumbs Also See for GT16:
Table of Contents

Advertisement

61.5.2 List of commands

The following shows the list of commands available in each data format.
List of commands for formats 1, 2 (GOT-A900 Series microcomputer connection)
Command
Command name
ASCII
Symbol
code
RD
52
44
Batch read in word units
H
H
WD
57
44
Batch read in word units
H
H
Random read in word
RR
52
52
H
H
*1
units
Random write in word
RW
52
57
H
H
*1
units
TR
54
52
Read clock data
H
H
TS
54
53
Set clock data
H
H
*1
Mixed specification of bit devices and word devices is also possible.
List of commands for formats 3 to 6 (A compatible 1C frame)
Command
Command name
ASCII
Symbol
code
BR
42
52
H
H
Batch read in bit units
JR
4A
52
H
H
WR
57
52
H
H
Batch read in word units
51
52
QR
H
H
BW
42
57
H
H
Batch write in bit units
JW
4A
57
H
H
WW
57
57
H
H
Batch read in word units
QW
51
57
H
H
BT
42
54
Test in bit units
H
H
JT
4A
54
(random write)
H
H
WT
57
54
Test in word units
H
H
QT
51
54
(random write)
H
H
*2
54
52
Read clock data
TR
H
H
*2
54
53
Set clock data
TS
H
H
*2
This is a dedicated command of GOT for the microcomputer connection.
*3
Specifies the address of bit devices in 16-point units. (Example: M0, M16, M32, and others)
Description
Reads bit devices in 16-point units.
Reads word devices in 1-point units.
Writes to bit devices in 16-point units.
Writes to word devices in 1-point units.
Reads multiple different bit devices in 16-point units.
Reads multiple different word devices in 1-point units.
Writes to multiple different bit devices in 16-point units.
Writes to multiple different word devices in 1-point units.
Reads the clock data of the GOT.
Sets the clock data of the GOT.
Description
Reads bit devices in 1-point units.
*3
Reads bit devices in 16-point units.
Reads word devices in 1-point units.
Writes to bit devices in 1-point units.
Writes to bit devices in 16-point units.
Writes to word devices in 1-point units.
Writes to multiple different bit devices in 1-point units.
Writes to multiple different bit devices in 16-point units.
Writes to multiple different word devices in 1-point units.
Reads the clock data of the GOT.
Sets the clock data of the GOT.
61. MICROCOMPUTER CONNECTION (SERIAL)
*3
*3
61.5 Message Formats
60
61
Max. number of points
processed
64 words (1024 points)
64 points
64 words (1024 points)
64 points
62
64 words (1024 points)
64 points
64 words (1024 points)
64 points
63
Max. number of points
processed
64
64 points
64 words (1024 points)
64 points
64 points
64 words (1024 points)
65
64 points
64 points
64 words (1024 points)
64 points
61 - 17

Advertisement

Table of Contents
loading

Table of Contents