61.4.5 SD devices

The SD devices are word devices into which GOT communication errors (error codes), clock data and other information
are stored.
List of SD devices
The following lists the SD devices (virtual devices inside the GOT).
Address
100ms counter (32bits)
The counter is incremented at 100ms intervals after GOT is turned ON.
(The time elapsed after GOT is turned ON is stored in 100ms units.)
(1) When setting the LH order to [32bit Storage] for the communication detail settings
The lower and upper bits are stored in SD0 and SD1 respectively.
SD0
SD1
(2) When setting the HL order to [32bit Storage] for the communication detail settings
The upper and lower bits are stored in SD0 and SD1 respectively.
Communication error status
An error data (error code) occurred during communication is stored.
•Host Address (Communication error that occurred on the request destination GOT)
0: No error
2: Framing error
4: Communication message error
*1
SD2
6: Clock data setting error
•Other station (Communication error that occurred on another GOT when multiple GOTs are connected)
101: Parity error
103: Overrun error
105: Timeout error (No station of the specified address exists.)
106: Multiple units not connectable 107: Clock data setting error
SD3
Clock data (second): Second data of 00 to 59 is stored.
SD4
Clock data (minute): Minute data of 00 to 59 is stored.
SD5
Clock data (hour): Hour data of 00 to 23 is stored.
SD6
Clock data (day): Day data of 00 to 31 is stored.
SD7
Clock data (month): Month data of 01 to 12 is stored.
Clock data (year)
SD8
4-digit year data is stored.
Clock data (day of week)
Day-of-the-week data is stored.
SD9
0: Sunday
4: Thursday
SD10 to 15
*1
For details and corrective actions for the errors (error codes) that are stored into SD2, refer to the following:
*2
If a wrong day of the week is set by the clock data setting commands, the clock data will differ from the time displayed on the
utility.
Example: When June 1, 2004 (Thursday) is set by the clock data setting command (the actual day of the week is Tuesday),
POINT
POINT
POINT
The side where virtual devices are set
System
: Set on the system side.
User
: Set on the user side (by sending request messages from host or using the touch switches, etc.
on the GOT).
SD1
Upper word
SD0
Upper word
1: Parity error
3: Overrun error
5: Command error
102: Framing error
104: Communication message error
*2
1: Monday
2: Tuesday
5: Friday
6: Saturday
■ Details and actions for errors (error codes) stored into SD2
"4" is stored to SD9 although Tuesday (TUE) will be displayed on the utility time display.
61. MICROCOMPUTER CONNECTION (SERIAL)
Description
SD0
Lower word
SD1
Lower word
3: Wednesday
Unused
61.4 Device Data Area
60
61
Set side
62
63
System
64
65
System
61 - 11