(3) AB Control/CompactLogix
Item
Set this item when change the
transmission speed used for
Transmission
communication with the connected
Speed
equipment.
(Default: 19200bps)
Set this item when change the data length
used for communication with the
Data Bit
connected equipment.
(Default: 8bits)
Specify the stop bit length for
Stop Bit
communications. (Default: 1bit)
Specify whether or not to perform a parity
Parity
check, and how it is performed during
communication. (Default: None)
Specify the format in which the sum check
is performed during communication when
Sum Check Type
performing sum check.
(Default: BCC)
Set the number of retries to be performed
Retry
when a communication error occurs.
(Default: 3times)
Set the time period for a communication to
Timeout Time
time out. (Default: 3sec)
Specify the adapter address (station No.
of the PLC that the GOT will monitor) in
Adapter Address
the connected network.
(Default: 0)
Specify the host address (station No. of
the adapter to which the GOT is
Host Address
connected) in the connected network.
(Default: 0)
Set this item to adjust the transmission
Delay Time
timing of the communication request from
the GOT. (Default: 0ms)
(4) AB SLC500
Item
Set this item when change the
transmission speed used for
Transmission
communication with the connected
Speed
equipment.
(Default: 19200bps)
Specify the adapter address (station
No. of the PLC that the GOT will
*1
Adapter Address
monitor) in the connected network.
(Default: 0)
Specify the host address (station No.
of the adapter to which the GOT is
*1
Host Address
connected) in the connected network.
(Default: 1)
*1
Do not specify the same value for the adapter address and
host address.
POINT
POINT
POINT
(1) Communication interface setting by the Utility
The communication interface setting can be changed
on the Utility's [Communication setting] after writing
[Communication Settings] of project data.
For details on the Utility, refer to the following.
12. COMMUNICATION INTERFACE SETTING
(COMMUNICATION SETTING)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
54 - 6
54. CONNECTION TO ALLEN-BRADLEY PLC
54.2 Serial Connection
Description
Range
9600bps,
19200bps,
38400bps,
57600bps
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
BCC,
CRC16
0 to 5times
3 to 30sec
0 to 254
0 to 254
0 to 300ms
Description
Range
4800bps,
9600bps,
19200bps
0 to 31
1 to 31
54.2.6 PLC Side Setting
POINT
POINT
POINT
ALLEN-BRADLEY PLC
For details of ALLEN-BRADLEY PLCs, refer to the
following manuals.
ALLEN-BRADLEY PLC user's Manual
Directly connecting to the CPU
Item
SLC500
Series
4800bps,
*1
9600bps,
Baud Rate
19200bps
Parity
EVEN
Control Line
Communication
Driver
Duplicate Packet
Detection
Station Address
Error Detection
BCC
*1
Set the Baud Rate according to the transmission speed
setting on the GOT side.
*2
Set the Error Detection according to the sum check format
setting on the GOT side.
Connecting to DH485 network via adapter
(1770-KF3) (Setting of Adapter)
Item
*1
Baud Rate
Parity
Flow Control
DF1 Device
DF1 half-duplex slave, local mode
Category
*2
Error Detection
DH-485 Baud Rate
Maximum Node
Address
DH-485 Node
Address
*1
Set the Baud Rate according to the transmission speed
setting on the GOT side.
*2
Set the Error Detection according to the sum check format
setting on the GOT side.
*3
For the Maximum Node Address, set the same address as
the Maximum Node Address on the DH-485 network.
*4
Set the DH-485 Node Address according to the Host
Address on the GOT side.
Set a unique DH-485 Node Address so that it does not
conflict with the Node Address of the PLC CPU on the DH-
485 network.
Setting details
Control/
MicroLogix
Compact/
1000/1200/
FlexLogix
1500 Series
Series
4800bps,
4800bps,
9600bps,
9600bps,
19200bps,
19200bps,
38400bps
38400bps
NONE
NONE
NO HANDSHAKING
DF1 HALF-DUPLEX SLAVE
DISABLE
0
*2
BCC, CRC
BCC, CRC
Setting details
4800bps, 9600bps, 19200bps
Even
Disable (No Handshaking)
BCC
19200bps
*3
1 to 31
*4
0 to 31
*2