53.5.7 Connecting to RB Series

Communication settings
Item
Communication protocol
1: MODBUS
Device address
1 to 99
*1
(Slave address)
2: 9600bps
*2
Communication speed
3: 19200bps
Data bit configuration
Refer to ■ Data bit configuration
Interval time
0 to 250
*1
When the setting value is set to 0, a communication is not
made.
*2
Adjust the settings with GOT settings.
Data bit configuration
Set value
Data bit
0
8
1
8
2
8
3
8
4
8
5
8
Communication setting mode
Set the communication setting mode using the
operation panel of the RB series main unit.
For details of the communication setting mode, refer to
the following.
RB series "Communication Instruction Manual"
53.5.8 Connecting to PF900
Communication settings
Make the communication settings by operating the key
of the temperature controller.
Item
9600bps, 19200bps, 38400bps,
*1
Communication speed1
57600bps
Communication protocol1
MODBUS
[8N1]: 8bit, None, 1bit
[8N2]: 8bit, None, 2bit
*1
[8E1]: 8bit, Even, 1bit
Data bit configuration1
[8E2]: 8bit, Even, 2bit
(Data bit, Parity bit, Stop bit)
[8O1]: 8bit, Odd, 1bit
[8O2]: 8bit, Odd, 2bit
*2
Device address1
1 to 99
(Slave address1)
*3
0 to 250 (ms)
Interval time
*1
Adjust the settings with GOT settings.
*2
Select the device address1 without overlapping with that of
other units.
*3
Set the maximum time from the sending of the last character
stop bit from the GOT side until the switching of the GOT
side to the receiving status (until the temperature controller
becomes ready to send). Set as necessary.
*4
When the setting value is set to 0, a communication is not
made.
53 - 20
53. CONNECTION TO RKC TEMPERATURE CONTROLLER
53.5 Temperature Controller Side Setting
Setting range
Parity bit
Stop bit
None
1
None
2
Even
1
Even
2
Odd
1
Odd
2
Setting range
*4
53.5.9 Connecting to HA400, HA900
Communication settings
Make the communication settings by operating the key
of the temperature controller.
(Communication 1)
Item
*1
9600bps, 19200bps, 38400bps
Communication speed1
[8N1]: 8bit, None, 1bit
[8N2]: 8bit, None, 2bit
*1
[8E1]: 8bit, Even, 1bit
Data bit configuration1
[8E2]: 8bit, Even, 2bit
(Data bit, Parity bit, Stop bit)
[8O1]: 8bit, Odd, 1bit
[8O2]: 8bit, Odd, 2bit
*2
Device address1
1 to 99
(Slave address1)
*3
0 to 250 (ms)
Interval time
(Communication 2)
Item
*1
9600bps, 19200bps, 38400bps
Communication speed2
[8N1]: 8bit, None, 1bit
[8N2]: 8bit, None, 2bit
*1
[8E1]: 8bit, Even, 1bit
Data bit configuration2
[8E2]: 8bit, Even, 2bit
(Data bit, Parity bit, Stop bit)
[8O1]: 8bit, Odd, 1bit
[8O2]: 8bit, Odd, 2bit
*2
Device address2
1 to 99
(Slave address2)
*3
0 to 250 (ms)
Interval time
*1
Adjust the settings with GOT settings.
*2
Select the device address1/2 without overlapping with that of
other units.
*3
Set the maximum time from the sending of the last character
stop bit from the GOT side until the switching of the GOT
side to the receiving status (until the temperature controller
becomes ready to send). Set as necessary.
*4
When the setting value is set to 0, a communication is not made.
53.5.10 Connecting to AG500
Communication settings
Make the communication settings by operating the key
of the temperature controller.
Item
*1
9600bps, 19200bps, 38400bps
Communication speed
Communication protocol
MODBUS
[8N1]: 8bit, None, 1bit
[8N2]: 8bit, None, 2bit
*1
[8E1]: 8bit, Even, 1bit
Data bit configuration
[8E2]: 8bit, Even, 2bit
(Data bit, Parity bit, Stop bit)
[8O1]: 8bit, Odd, 1bit
[8O2]: 8bit, Odd, 2bit
*2
Device address
1 to 99
(Slave address)
*3
0 to 250 (ms)
Interval time
*1
Adjust the settings with GOT settings.
*2
Select the device address1 without overlapping with that of
other units.
*3
Set the maximum time from the sending of the last character
stop bit from the GOT side until the switching of the GOT
side to the receiving status (until the temperature controller
becomes ready to send). Set as necessary.
*4
When the setting value is set to 0, a communication is not made.
Setting range
*4
Setting range
*4
Setting range
*4