54.3 Ethernet Connection
54.3.1 System configuration for connecting to ControlLogix or CompactLogix
EtherNet/IP
ControlLogix,
communication
CompactLogix
module
PLC
EtherNet/IP
Communication
communication
Series
*1
module
*4
1756-ENET
(10Mbps)
*4
1756-ENBT
ControlLogix
Ethernet
(10/100Mbps)
*4
1756-EN2TR
(10/100Mbps)
CompactLogix
-
Ethernet
*1
Allen-Bradley product manufactured by Rockwell Automation, Inc. For details of the product, contact Rockwell Automation, Inc.
*2
The destination connected with the twisted pair cable varies with the configuration of the applicable Ethernet network system.
Connect to the Ethernet module, hub, transceiver or other system equipment corresponding to the applicable Ethernet network system.
Use cables, connectors, and hubs that meet the IEEE802.3 10BASE-T/100BASE-TX standards.
The use of shielded twisted pair cable (STP) is recommended in environments in which the performance against noise is required.
*3
A length between a hub and a node.
The maximum distance differs depending on the Ethernet device to be used.
The following shows the number of the connectable nodes when a repeater hub is used.
• 10BASE-T: Max. 4 nodes for a cascade connection (500m)
• 100BASE-TX: Max. 2 nodes for a cascade connection (205m)
When switching hubs are used, the cascade connection between the switching hubs has no logical limit for the number of cascades.
For the limit, contact the switching hub manufacturer.
*4
The connectable Ethernet/IP communication are only GT1455-QTBDE and GT1450-QLBDE.
(ControlLogix5550/5555/5560)
1756-ENET (10Mbps), 1756-ENBT (10/100Mbps)
(ControlLogix5570)
1756-EN2TR (10/100Mbps)
*5
The number of the connectable GOTs for 1 PLC differs depending on the PLC series.
(ControlLogix5550/5555/5560)
• When PLC: GOT is N:1, the following number of the PLCs can be connected to 1 GOT.
TCP: 128 or less
• When PLC: GOT is 1:N, the following number of the GOTs can be connected to 1 PLC.
TCP: 64 or less (recommended to 16 or less)
(ControlLogix5570)
• When PLC: GOT is N:1, the following number of the PLCs can be connected to 1 GOT.
TCP: 128 or less
• When PLC: GOT is 1:N, the following number of the GOTs can be connected to 1 PLC.
TCP: 128 or less (reccomended to 16 or less)
Connection cable
Connection cable
*2
Cable model
Type
• 10BASE-T
Shielded twisted pair
cable (STP) or
unshielded twisted
pair cable (UTP) :
Category 3, 4, and 5
• 100BASE-TX
Shielded twisted
pair cable (STP) :
Category 5 and 5e
• 10BASE-T
Shielded twisted pair
cable (STP) or
unshielded twisted
pair cable (UTP) :
Category 3, 4, and 5
• 100BASE-TX
Shielded twisted
pair cable (STP) :
Category 5 and 5e
Connector
conversion
box
External cable
Connector
External cable
conversion box
GT16H-C30-42P(3m)
GT16H-CNB-42S
GT16H-C60-42P(6m)
GT16H-C100-42P(10m)
GT16H-C30-37PE(3m)
GT16H-CNB-37S
GT16H-C60-37PE(6m)
GT16H-C100-37PE(10m)
GT16H-C30-42P(3m)
GT16H-CNB-42S
GT16H-C60-42P(6m)
GT16H-C100-42P(10m)
GT16H-C30-37PE(3m)
GT16H-CNB-37S
GT16H-C60-37PE(6m)
GT16H-C100-37PE(10m)
54. CONNECTION TO ALLEN-BRADLEY PLC
54.3 Ethernet Connection
Communication driver
Ethernet/IP(AB), Gateway
GOT
Maximum
GOT
Number of connectable
segment
Model
equipment
*3
length
100m
*5
When PLC: GOT is N:1
The following shows
the number of PLCs for
1 GOT
TCP: 128 or less
When PLC: GOT is 1:N
100m
The following shows
the number of GOTs for
1 PLC
TCP: 32 or less
(recommended to 16 or
less)
54 - 7
52
53
54
55
56
57
58
59