55.4 GOT Side Settings
55.4.1 Setting communication
interface (Communication
settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: GE
• Controller Type: GE Series 90
• I/F: Interface to be used
• Driver: GE (SNP-X)
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
55.4.2 Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
16.1.2 I/F communication setting
55 - 10
55. CONNECTION TO GE PLC
55.4 GOT Side Settings
3.
4.
Click!
[Controller Setting] from the
55.4.2 Communication detail settings
Make the settings according to the usage environment.
Item
Set this item when change the
transmission speed used for
Transmission
communication with the connected
Speed
equipment.
(Default: 19200bps)
Set this item when change the data
length used for communication with
*1
Data Bit
the connected equipment.
(Default: 8bits)
Specify the stop bit length for
Stop Bit
communications.
(Default: 1bit)
Specify whether or not to perform a
parity check, and how it is performed
Parity
during communication.
(Default: Odd)
Set the number of retries to be
performed when a communication
Retry
error occurs.
(Default: 3times)
Set the time period for a
Timeout Time
communication to time out.
(Default: 3sec)
Specify the host address (station No.
of the GOT to which the PLC is
Host Address
connected) in the connected network.
(Default: 00)
Set this item to adjust the
transmission timing of the
Delay Time
communication request from the
GOT.
(Default: 5ms)
*1
If no setting is provided for the data length for the controller,
set "8 bits".
If the setting is provided for the data length for the controller,
set the same set value for the data length for the GOT as
that for the PLC.
POINT
POINT
POINT
(1) Communication interface setting by the Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
12. COMMUNICATION INTERFACE SETTING
(COMMUNICATION SETTING)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
Description
Range
9600bps
19200bps
38400bps
57600bps
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
0 to 5times
3 to 30sec
00 to 31
0 to 300ms