54.2.5 GOT Side Settings
Setting communication interface
(Communication settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
[Controller Setting] from the menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: AB
• Controller Type: Set either of the followings.
• SLC500
• MicroLogix1000/1200/1400/1500 series
• Control/CompactLogix
• I/F: Interface to be used
• Driver: Set either of the followings.
• When connecting to SLC500 Series: AB SLC500
AB 1:N
• When connecting to MicroLogix1000/1200/1400/
1500 Series: AB MicroLogix
• When connecting to Control/Compact/FlexLogix
Series: AB Control/CompactLogix
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage environment.
54.2.5 ■ Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
3.
Communication detail settings
(1) AB SLC500
4.
Item
Transmission
Speed
Click!
Adapter Address
Host Address
*1
(2) AB MicroLogix
Item
Transmission
Speed
,
Sum Check Type
Adapter Address
Host Address
*1
54. CONNECTION TO ALLEN-BRADLEY PLC
17.1.2 I/F communication setting
AB 1: N
,
Description
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 19200bps)
Specify the adapter address (station
No. of the PLC that the GOT will
*1
monitor) in the connected network.
(Default: 0)
Specify the host address (station No.
of the adapter to which the GOT is
*1
connected) in the connected network.
(Default: 1)
Do not specify the same value for the adapter address and
host address.
Description
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 19200bps)
Specify the format in which the sum
check is performed during
communication when performing sum
check.
(Default: BCC)
Specify the adapter address (station
No. of the PLC that the GOT will
*1
monitor) in the connected network.
(Default: 0)
Specify the host address (station No.
of the adapter to which the GOT is
*1
connected) in the connected network.
(Default: 1)
Do not specify the same value for the adapter address and
host address.
54.2 Serial Connection
52
53
54
Range
4800bps,
9600bps,
19200bps
55
0 to 31
1 to 31
56
Range
4800bps,
9600bps,
19200bps,
38400bps
57
BCC, CRC16
0 to 63
58
0 to 63
59
54 - 5