Mitsubishi Electric MELSEC iQ-R Series User Manual page 543

Motion module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error
Error
Error name
code
(System/
(Hexad
axis/axes
ecimal)
group)
1A79H
Axis
Out of Forward
Direction Torque Limit
Initial Value
Specification Range
1A7AH
Axis
Out of Reverse
Direction Torque Limit
Initial Value
Specification Range
1A7BH
Axes group
Insufficient Movement
Amount at Changing
Target Address
1A7CH
Axes group
Operation FB Issue
Error to the Axis during
Axis Group Operating
1A7EH
Axis/Axes
Overrun Error
group
1A7FH
Axes group
Driver Emulation Switch
Error
1A80H
Axis/Axes
BufferMode
group
Specification Disabled
1A85H
Axis
Out of Frequency
Specification Range
1A86H
Axis
Out of Filter Operation
Specification Range
1A87H
Axis
Out of Direction Limit
Value Specification
Range
1A8AH
Axis
Out of Overrun
Operation Setting
Range
Error detail and cause
Detection
timing (At
start/
during
control
The value larger than
At power ON
"AxisName.PrConst.TorqueLimit_
Max" was set to
"AxisName.PrConst.TorqueLimit_
PositiveInitial".
The value larger than
At power ON
"AxisName.PrConst.TorqueLimit_
Max" was set to
"AxisName.PrConst.TorqueLimit_
NegativeInitial".
Movement amount became 0
During
after changing target position/
control
movement distance at multiple
axes interpolation control of
reference axis/long axis speed
designation.
Multiple start of single axis control
At start
FB was executed for operating
axis in axis group.
• Overrun occurred since the
Controlling
deceleration distance for output
At multipul
speed was not reached while
start
detecting the last positioning
At control
address.
change
• Positioning direction is inverted
when multiple start is executed
by Aborting.
• Positioning direction is inverted
when target position is
changed.
Driver emulation switch was
When
executed when
executing
"AxisName.Md.AxisStatus" is
driver
other than Disable or Standstill.
emulate
switching
Multiple start was executed in
At multipul
combination disable BufferMode.
start
The value is out of range for
At start
"Frequency".
The value is out of range for
At start
"Filter".
The value is out of range for
At start
"PositiveLimit", "NegativeLimit".
At start
The value is out of range for
"AxisName(AxesGroupName).Pr.
OverrunOperation".
Operation at
Remedy
error
occurrence
Generating axis fails.
Set
"AxisName.TorqueLimit_
PositiveInitial" within the
range of 0 to
"AxisName.PrConst.Tor
queLimit_Max".
Generating axis fails.
Set
"AxisName.PrConst.Tor
queLimit_NegativeInitial"
within the range of 0 to
"AxisName.PrConst.Tor
queLimit_Max".
Stops the operation.
Set target position/
movement distance so
that movement amount
is not insufficient.
Stops the operation.
Execute multiple start of
multiple axes control FB
for the axis of axis group
operating.
Stops the operation.
Set "Velocity" "Position"/
"Distance"
"Deceleration" so that an
overrun will not occur.
Stops.
Driver emulation switch
was executed when
"AxisName.Md.AxisStatu
s" is other than Disable
or Standstill.
Stops.
Multiple start was
executed in combination
disable BufferMode.
Not start.
The value is out of range
for "Frequency".
Not start.
The value is out of range
for "Filter".
Not start.
Set "PositiveLimit",
"NegativeLimit" within
the range.
Not start.
Set
"AxisName(AxesGroupN
ame).Pr.OverrunOperati
on" within the range.
22 TROUBLESHOOTING
22.5 List of Error Codes