13.5 ZONE Outputs

13.5.2 Parameters Related to ZONE Signals

13.5.2 Parameters Related to ZONE Signals

With the following parameter, the initial status* of the programmable output signals (/POUT0 to
/POUT7) can be set to ZONE signals.
The initial status is the status that exists after the control power supply is turned ON or after
resetting the SERVOPACK.
Parameter
PnB4F
Note: You can set the ZONE signals for /POUT5 to /POUT7, but the outputs will always be OFF.

13.5.3 SigmaWin+ Procedures

You use the SigmaWin+ to edit, write, and save the ZONE table.
Use the following flow.
13-54
0000h
When the control power supply is turned ON or the
(default
SERVOPACK is reset, the /POUT0 to /POUT7 sig-
nals are turned OFF.
setting)
When control power is turned ON or SERVOPACK
0001h
is reset, signals /POUT0 to 7 are ZONE signals.
Editing the ZONE Table
Writing the ZONE Table
Saving the ZONE Table
Checking the Operation of the ZONE Table
Meaning
Editing the ZONE Table on page 13-55
Writing the ZONE Table on page 13-56
Saving the ZONE Table on page 13-58
When Enabled Classification
After restart
Setup