15.2 Alarm Displays
15.2.2 Troubleshooting Alarms
Alarm Number:
Alarm Name
A.100:
Overcurrent
Detected
(An overcurrent
flowed through
the power trans-
former or the heat
sink overheated.)
15-16
Possible Cause
The Main Circuit
Cable is not wired
Check the wiring.
correctly or there is
faulty contact.
Check for short-circuits
across Servomotor
There is a short-circuit
phases U, V, and W, or
or ground fault in a
between the ground
Main Circuit Cable.
and Servomotor phases
U, V, and W.
Check for short-circuits
across Servomotor
There is a short-circuit
phases U, V, and W, or
or ground fault inside
between the ground
the Servomotor.
and Servomotor phases
U, V, or W.
Check for short-circuits
across the Servomotor
There is a short-circuit
connection terminals U,
or ground fault inside
V, and W on the SER-
the SERVOPACK.
VOPACK, or between
the ground and termi-
nals U, V, or W.
The regenerative
resistor is not wired
Check the wiring.
correctly or there is
faulty contact.
Check the power con-
The dynamic brake
sumed by the DB resis-
(DB, emergency stop
tor to see how
executed from the
frequently the DB is
SERVOPACK) was
being used. Or, check
frequently activated,
the alarm display to see
or a DB overload
if a DB overload alarm
alarm occurred.
(A.730 or A.731) has
occurred.
Check the regenerative
load ratio in the Sig-
The regenerative pro-
maWin+ Motion Monitor
cessing capacity was
Tab Page to see how
exceeded.
frequently the regenera-
tive resistor is being
used.
Check the regenerative
load ratio in the Sig-
The SERVOPACK
maWin+ Motion Monitor
regenerative resis-
Tab Page to see how
tance is too small.
frequently the regenera-
tive resistor is being
used.
Confirmation
Correct the wiring.
The cable may be short-
circuited. Replace the
cable.
The Servomotor may be
faulty. Replace the Servo-
motor.
The SERVOPACK may be
faulty. Replace the SER-
VOPACK.
Correct the wiring.
Change the SERVOPACK
model, operating meth-
ods, or the mechanisms
so that the dynamic brake
does not need to be used
so frequently.
Recheck the operating
conditions and load.
Change the regenerative
resistance to a value
larger than the SERVO-
PACK minimum allowable
resistance.
Continued from previous page.
Correction
Reference
page 4-26
page 4-22
*3
Continued on next page.