INDEXER Alarm Reset (FnB0C)
This function resets alarms at both the SERVOPACK and INDEXER Module, and clears the
alarm history at the INDEXER Module.
• INDEXER Module alarms are not reset by the "ALARM RESET" button of the digital operator. To
reset INDEXER Module alarms, execute alarm resetting with FnB0C.
• Eliminate the causes of alarms before resetting them.
• When you execute Fn006, only the SERVOPACK alarm history is cleared. The INDEXER Mod-
Important
ule alarm history is not cleared. To clear the INDEXER Module alarm history, execute alarm his-
tory clearance with FnB0C.
 Preparation
 When Resetting Alarms
None
 When Clearing the Alarm History
The following conditions must be met to reset INDEXER alarms.
• The write-prohibited setting (Fn010) must not be set to write-protect parameters.
• The ALMTRCCLR command must not being executed.
• The RES command must not being executed.
 Operating Procedure
Step
Display after Operation
1
2
3-1
3-2
4
5
17.2.2 Operation of Utility Functions
Keys
Press the
key to open the Utility Function
Mode main menu, and move the cursor with the
keys to select FnB0C.
Press the
key to view the FnB0C operation
screen.
 When Resetting Alarms
Use the
 When Clearing the Alarm History
Use the
Press the
key to reset the alarms or clear the
alarm history.*
To cancel the FnB0C operation, press the
key before pressing the
returns to the Utility Function Mode main menu
without executing the operation.
When alarm resetting or alarm history clearance
is completed, the display returns to the Mode
selection screen.
17.2 Operation of Digital Operator
Operation
keys to select "ALM state".
keys to select "ALM History".
key. The display
Continued on next page.
17
17-29