Pausing Registration
This example shows how to turn OFF the /START-STOP signal to temporarily stop registration
operation and then turn ON the /START-STOP signal to restart registration operation.
The program table for this positioning is shown below.
PGM-
POS
SPD
STEP
0
I+200000
30000
1
I-200000
30000
• Operating Procedure
Turn ON the /MODE 0/1 signal to change to mode 0.
Set the /SEL0 to /SEL7 signals to 0 to specify program step 0.
Turn ON the /START-STOP signal to start program table operation.
The /INPOSITION signal turns OFF.
The /RGRT signal turns ON to perform registration operation.
The speed changes to the registration speed.
Turn OFF the /START-STOP signal to stop operation.
Turn ON the /START-STOP signal to restart program table operation.
The /INPOSITION turns ON when positioning is completed for the remaining registration
distance.
When execution of program step 1 starts, the /INPOSITION signal turns OFF.
The /RGRT signal turns ON to perform registration operation.
The speed changes to the registration speed.
The /INPOSITION turns ON when positioning is completed for the registration distance.
• Operation Pattern and Related Signal Timing
Speed
Operation
Pattern
Mode 0
(Program Table Operation)
/MODE 0/1
4 ms min.
START-STOP*
2 ms min.
/SEL0 to /SEL7*
/RGRT
/INPOSITION
*
Do not change /SEL0 to /SEL7 for 4 ms after turning ON the /START-STOP signal.
RDST
RSPD
ACC
100000
15000
400000 200000 NNNNNNNN
100000
15000
:
Step 0
200
μs min.
13.3 Program Table Operation
13.3.8 Program Table Operation Examples
DEC
POUT
EVENT
IT0
:
: : : : : : : :
IT0
Step 1
0
LOOP
NEXT
1
1
1
END
Time
13
13-37