Preventative Maintenance - YASKAWA E-7S SERVOPACK SGD7S Product Manual

E-7-series ac servo drive e-7s servopack command option attachable type with indexer module
Table of Contents

Advertisement

9.4 Monitoring Product Life

9.4.3 Preventative Maintenance

9.4.3

Preventative Maintenance

You can use preventative maintenance warnings for preventative maintenance. The SERVO-
PACK can notify the host controller when it is time to replace any of the main parts.
Preventative Maintenance Warning
An A.9b0 warning (Preventative Maintenance Warning) is detected when any of the following
service life prediction values drops to 10% or less: SERVOPACK built-in fan life, capacitor life,
inrush current limiting circuit life, and dynamic brake circuit life. You can change the setting of
Pn00F = n.X to enable or disable these warnings.
Pn00F
9-16
Parameter

n.
0
Do not detect preventative maintenance warnings.
(default setting)

n.
1
Detect preventative maintenance warnings.
Description
When
Classifi-
Enabled
cation
After
Setup
restart

Hide quick links:

Advertisement

Table of Contents
loading