Restoring Data From An Unencrypted Backup File - Siemens SINAMICS SIMOTICS S200 PROFINET Operating Instructions Manual

Servo drive system
Table of Contents

Advertisement

Corrective maintenance
13.1 Service and maintenance for the converter
• Scenario 1: The target converter has the same or a higher firmware version.
– If the drive data are restored from an encrypted backup file, then proceed as follows, see
– If the drive data are restored from an unencrypted backup file, then proceed as follows,
• Scenario 2: The target converter has an older firmware version.
– The operation is canceled.
– Restore the firmware to the version of the source converter. The firmware version can be ≥
– Proceed as described in scenario 1.
Result
When running up, the converter retrieves the settings from the backup file. Commissioning has
been completed once the converter has run up.
More information
• Update the connected components:
When the converter runs up after being restored, the connected components are updated.
The converter must then be switched off and switched on.
13.1.3.2

Restoring data from an unencrypted backup file

Requirement
• You have an unencrypted backup file of the source converter on your operating unit.
• Rights required for active user management (UMAC):
– "Create backup or load drive data to Startdrive"
Procedure
1. Call menu "Backup and restore" in the web server.
2. Navigate to the "Restore drive data from backup file" area.
3. Use the "Click to select file, or drag and drop file here" button to select the backup file.
4. To restore the drive data, proceed as described below depending on the specific application.
This step is included in the following diagrams as step 3.
594
Section "Restoring data from an encrypted backup file (Page 596)".
see Section "Restoring data from an unencrypted backup file (Page 594)".
firmware version of the source converter.
Note
Determining the firmware version of the source converter
Review the machine documentation. Alternatively: Check which firmware version is
installed on the other converters of the same type in the machine.
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB