Message value:
-
Component:
Control Unit (CU)
Response:
NONE
Acknowledgment: NONE
Cause:
- For the converter, the options that require a license are being used but the licenses are not sufficient.
- An error occurred when checking the existing licenses.
Alarm value (r2124, interpret decimal):
0: The existing license is not sufficient.
1: An adequate license was not able to be determined as the memory card with the required licensing data was withdrawn
in operation or the memory card has developed a defect.
2: An adequate license was not able to be determined as there is no licensing data available on the memory card.
3: An adequate license was not able to be determined as there is no licensing data available on the memory card.
4, 5, 6, 7: An adequate license was not able to be determined as the licensing data were manipulated and are therefore
invalid.
8,9: An internal error occurred when checking the license.
Remedy:
For alarm value = 0:
Additional licenses are required and must be activated.
For alarm value = 1:
Reinsert or replace the memory card that matches the system.
For alarm value = 2:
Transfer the license file to the converter.
For alarm value = 3:
Compare the license file name (after "LK_" to ".ZIP") with the serial number of the memory card.
Transfer the appropriate license file to the converter.
For alarm value = 4, 5, 6, 7, 8, 9:
- Carry out a POWER ON.
- Upgrade firmware to later version.
- Contact Technical Support.
Note:
An overview of the converter functions requiring a license can be displayed using a commissioning tool in the online mode.
Depending on the commissioning tool, you can also obtain the necessary licensing (serial number, license file, Trial License
Mode).
A13030
Trial License activated
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Message value:
-
Component:
Control Unit (CU)
Response:
NONE
Acknowledgment: NONE
Cause:
The "Trial License" function was activated. One of the available periods is expiring.
Remedy:
Not necessary.
The alarm is automatically withdrawn after the periods have expired.
A13031
Trial License period expired
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Message value:
-
Component:
Control Unit (CU)
Response:
NONE
Acknowledgment: NONE
Cause:
One of the available periods of the "Trial License" function has expired.
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB
System messages
12.3 Faults and alarms
539