Corrective maintenance
13.1 Service and maintenance for the converter
– Enter the drive password of the source converter.
• Scenario 3: A different drive password is configured in the target converter and the source
converter.
1
– Click on "Restore".
– Enter the drive password of the target converter.
– Enter the drive password of the source converter.
13.1.4

Forming the DC link capacitors

Overview
If the converter has been out of operation for too long, you must form the DC link capacitors
before connecting the full line voltage to the converter. Non-formed DC link capacitors can
damage the converter in operation.
Forming can be omitted if the line voltage is applied to the converter once a year for one
hour.
598
The drive data are loaded into the converter from the backup file.
As a consequence, the status of the settings at the instant of the backup are restored.
Function "Drive data encryption" is activated. The drive password of the source converter
is transferred to the target converter.
A dialog to enter the password opens.
A dialog to enter the password opens.
The drive data are loaded into the converter from the backup file.
As a consequence, the status of the settings at the instant of the backup are restored.
Function "Drive data encryption" is activated. The drive password of the source converter
is transferred to the target converter. When doing this, the drive password of the target
converter is overwritten.