System messages
12.3 Faults and alarms
Acknowledgment: IMMEDIATELY
Cause:
Too many safety messages have occurred within a short time so that some have not been able to be displayed.
Remedy:
No remedy required
F01800
Internal communications faulted
Message class:
Internal (DRIVE-CLiQ) communication error (12)
Message value:
%1
Component:
None
Response:
NONE
Acknowledgment: IMMEDIATELY
Cause:
 
Remedy:
Replace the component involved.
A01900
PN: Configuration telegram error
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Message value:
%1
Component:
None
Response:
NONE
Acknowledgment: NONE
A controller attempts to establish a connection using an incorrect configuring telegram.
Cause:
Alarm value (r2124, interpret decimal):
2:
Too many PZD data words for output or input. The number of possible PZD is specified by the number of indices in r2050/
r2053.
3:
Uneven number of bytes for input or output.
4:
Setting data for synchronization not accepted. For more information, see A01902.
211:
Unknown parameterizing block.
Additional values:
Only for internal Siemens troubleshooting.
Remedy:
Check the bus configuration on the controller and device sides.
A01902
PN: Isochronous operation parameterization not permissible
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Message value:
%1
Component:
None
Response:
NONE
Acknowledgment: NONE
486
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB