Siemens SINAMICS SIMOTICS S200 PROFINET Operating Instructions Manual page 469

Servo drive system
Table of Contents

Advertisement

Remedy:
Adapting topologies:
- Change over the actual topology to match the target topology.
- Load the target topology that matches the actual topology (commissioning tool).
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
F01451
Topology: Target topology is invalid
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Message value:
%1
Component:
None
Response:
NONE
Acknowledgment: IMMEDIATELY
Cause:
An error was detected in the target topology.
The target topology is invalid.
Fault value (r0949, interpret hexadecimal):
ccccbbaa hex: cccc = index error, bb = component number, aa = fault cause
aa = 1B hex = 27 dec: Error not specified.
aa = 1C hex = 28 dec: Value illegal.
aa = 1D hex = 29 dec: Incorrect ID.
aa = 1E hex = 30 dec: Incorrect ID length.
aa = 1F hex = 31 dec: Too few indices left.
aa = 20 hex = 32 dec: component is not connected to the converter.
Remedy:
Download the target topology again using the commissioning tool.
A01481
Topology: Internal communications faulted
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Message value:
Component: %1, to %2, %3, connection: %4
Component:
None
Response:
NONE
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB
System messages
12.3 Faults and alarms
467