Protective conductor for the mains supply cable
The protective conductor must be dimensioned in compliance with local installation rules for
equipment with high leakage currents. As a minimum, one of the following conditions must be
satisfied:
•
The protective conductor is routed so that along its complete length it is protected against
mechanical damage.
•
The protective conductor has a cross-section ≥ 10 mm² Cu.
•
A second protective conductor with the same cross-section is provided.
•
The protective conductor of a multi-conductor cable has a cross-section ≥ 2.5 mm² Cu.
Protective conductor of the converter line supply cable
The protective conductor must be dimensioned in compliance with local installation rules.
•
If each converter is individually protected, the protective conductor with the same cross-sec‐
tion must be routed in the same way as the line connection cable to the converter.
Protective conductor between PE and control cabinet
The cable cross-section must be dimensioned in compliance with local installation rules.
Protective conductor of the motor power cable
The protective conductor has the same cross-section as the line conductor of the motor power
cable.