SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB
Protective conductor for the mains supply cable
The protective conductor must be dimensioned in compliance with local installation rules for
equipment with high leakage currents. As a minimum, one of the following conditions must be
satisfied:
The protective conductor is routed so that along its complete length it is protected against
mechanical damage.
The protective conductor has a cross-section ≥ 10 mm² Cu.
A second protective conductor with the same cross-section is provided.
The protective conductor of a multi-conductor cable has a cross-section ≥ 2.5 mm² Cu.
Protective conductor of the converter line supply cable
The protective conductor must be dimensioned in compliance with local installation rules.
If each converter is individually protected, the protective conductor with the same cross-sec‐
tion must be routed in the same way as the line connection cable to the converter.
Protective conductor between PE and control cabinet
The cable cross-section must be dimensioned in compliance with local installation rules.
Protective conductor of the motor power cable
The protective conductor has the same cross-section as the line conductor of the motor power
cable.
4.6 Minimum cross-section of the protective conductors
Application planning
87