Setting motor overload protection in accordance with UL 61800-5-1 Ed.2

Overview
The motor overload protection function works without temperature sensors in the 1FL2 motors.
To comply with UL 61800‑5‑1 Ed.2, you must make some additional settings when operating
the converter with a 1FL2 motor.
Requirement
• You have completed quick commissioning with the correct motor data.
Procedure
Proceed as follows to activate the motor overload protection according to UL 61800‑5‑1 Ed.2:
1. Set p5375.0 = 1
2. Set p5375.1 = 1
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB
Functions
10.5 General functions
367