Siemens SINAMICS SIMOTICS S200 PROFINET Operating Instructions Manual page 570

Servo drive system
Table of Contents

Advertisement

System messages
12.3 Faults and alarms
Message value:
%1
Component:
Power Unit
Response:
OFF2
Acknowledgment: IMMEDIATELY
Cause:
A checksum error (CRC error) has occurred for the power unit.
Remedy:
- Carry out a POWER ON (switch-off/switch-on) for all components.
- Upgrade firmware to later version.
- Contact Technical Support.
F30805
Power unit: EEPROM checksum error
Message class:
Hardware/software error (1)
Message value:
%1
Component:
Power Unit
Response:
OFF2
Acknowledgment: IMMEDIATELY
Cause:
Internal parameter data is corrupted.
Fault value (r0949, interpret hexadecimal):
01: EEPROM access error.
02: Too many blocks in the EEPROM.
Remedy:
Replace the module.
F30809
Power unit: Switching information not valid
Message class:
Hardware/software error (1)
Message value:
-
Component:
Power Unit
Response:
OFF2
Acknowledgment: IMMEDIATELY
Cause:
For 3P gating unit, the following applies:
The last switching status word in the setpoint telegram is identified by the end ID. Such an end ID was not found.
Remedy:
- Carry out a POWER ON (switch-off/switch-on) for all components.
- Upgrade firmware to later version.
- Contact Technical Support.
F30810
Power unit: Watchdog timer expired
Message class:
Hardware/software error (1)
Message value:
-
Component:
Power Unit
Response:
OFF2
Acknowledgment: IMMEDIATELY
Cause:
The watchdog timer has expired. This can only be caused by a fatal software error.
Remedy:
- Carry out a POWER ON (switch-off/switch-on) for all components.
- Upgrade firmware to later version.
- Contact Technical Support.
F30815
Power unit: Processor clock signal error
Message class:
Hardware/software error (1)
Message value:
-
Component:
Power Unit
Response:
OFF2
568